Thermal power | 8,7–56,2* kW |
---|---|
Efficiency: | 4600 m3/h |
Mass: | 27,3 kg |
Colour: | grey (RAL 9006) |
Cover: | ABS plastic |
Fan heater designed to operate indoors.
The AGRO SP is equipped with special fan with protection degree IP66 and heat exchanger covered with protective coating resistant to corrosion. Lamellas on the exchanger are thicker than ordinary and can be cleaned with pressured air. Additionally, clamps which connect the confusor to the heat exchanger enable easy access to the inside of the unit. Such a construction makes the maintenance operations faster and helps in maintaining the unit clean and in optimal condition.
AGRO SP heaters are designed to operate in aggressive conditions so they are perfect for agricultural buildings, where there is high contamination of the air, high humidity and corrosion environment. Main purposes: poultry farms, dryers, etc.
All of the FLOWAIR products have a complete control system. AGRO SP units are available with simple ON/OFF control system, which has low investment cost.
AGRO SP | |
Max. air flow [m3/h]* | 4600 |
Max. air flow range with outlet grille [m]** | 28 |
Max. air flow range without outlet grille [m]** | 12 |
Power supply [V/Hz] | 230 / 50 |
Max. current consumption [A] | 2,5 |
Max. power consumption [W] | 360 |
IP / Insulation class | 66 / F |
Max. acoustic pressure level [dB(A)]*** | 68,7 |
Max. heating water temperature [oC] | 95 |
Max. operating pressure [MPa] | 1,6 |
Connection ["] | ¾” |
Weight [kg] | 27,3 |
Weight of unit filled with water [kg] | 31 |
* Without 6-side outlet diffuser SP/HP
** Range of horizontal isothermal air stream, at 0,5 m/s velocity limit
*** Acoustic pressure level at a distance of 5 m from the unit, in the room of medium capabillity of sound absorption and 1500 m3 of cubic measure.
AGRO SP | ||||||||||||||||||||
V = 4600m3/h | ||||||||||||||||||||
Tp1 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 | PT | Qw | ∆pw | Tp2 |
°C | kW | l/h | kPa | °C | kW | l/h | kPa | °C | kW | l/h | kPa | °C | kW | l/h | kPa | °C | kW | l/h | kPa | °C |
Tw1/Tw2 = 90/70°C | Tw1/Tw2 = 80/60°C | Tw1/Tw2 = 70/50°C | Tw1/Tw2 = 60/40°C | Tw1/Tw2 = 50/40°C | ||||||||||||||||
0 | 56,2 | 2480 | 20,0 | 34,0 | 48,6 | 2140 | 16,0 | 29,5 | 41 | 1800 | 12,0 | 25,0 | 33,4 | 1450 | 9,0 | 20,0 | 31,2 | 2710 | 26,0 | 19,0 |
5 | 52,0 | 2290 | 17,0 | 37,0 | 44,5 | 1950 | 13,0 | 32,5 | 36,9 | 1620 | 11,0 | 28,0 | 29,4 | 1280 | 7,0 | 23,0 | 27,2 | 2370 | 20,0 | 22,0 |
10 | 47,8 | 2110 | 15,0 | 40,0 | 40,4 | 1780 | 11,0 | 35,5 | 33 | 1440 | 9,0 | 30,5 | 25,5 | 1110 | 7,0 | 26,0 | 23,4 | 2030 | 15,0 | 24,5 |
15 | 43,8 | 1930 | 13,0 | 43,0 | 36,4 | 1600 | 10,0 | 38,0 | 29,1 | 1270 | 7,0 | 33,5 | 21,6 | 940 | 5,0 | 29,0 | 19,6 | 1710 | 12,0 | 27,5 |
20 | 39,8 | 1750 | 11,0 | 46,0 | 32,6 | 1430 | 8,0 | 41,0 | 25,3 | 1110 | 6,0 | 36,5 | 17,9 | 780 | 4,0 | 31,5 | 15,9 | 1380 | 8,0 | 30,5 |
V – air flow
PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water stream flow in the heat exchanger
Δpw – water pressure drop in heat exchanger
AGRO SP fan heaters can be installed on the vertical partitions in the buildings or under the ceiling with 6-sided air diffuser.
|
|
AGRO SP/HP 6-sided air diffuser the use of the diffuser causes steady air |
Rotary console AGRO SP enables 170° rotation of the device |