Products

AGRO HT


Basic parameters:

Thermal power 19,2 - 158* kW
Efficiency: 9 000 — 10 000 m3/h
Mass: 73-85 kg
Colour: red-black**
Cover: ABS plastic

*min: temperature of heating medium 40/30°C, air temperature at the inlet 20°C,
max: temperature of heating medium 90/70°C, air temperature at the inlet 0°C
**RAL 3020 and RAL 9005


Basic files

Product indexes:
54057, 54058

CHARACTERISTIC:

The fan heater is dedicated for use inside buildings.


Fan is equipped with three phase IP55 motor. Heater exchanger coated with special cataphoresis layer proof the unit against corrosion. Lamellas on the exchanger are thicker than ordinary and can be cleaned with pressured water. Additionally, locking latches give easy access to interior of the unit what significantly reduces time of service and maintenance work. Hinged construction and special opening clamps make it possible to use the unit as an air mixer.

Application:

AGRO HT is designated for agricultural facilities, mainly poultry farms, piggeries and corrosive environment. 

Control:

AGRO HT fan heaters can be controlled with FLOWAIR standard automatics (details in operation and maintenance documentation) or with a microclimate controller.

Technology /Innovation/Benefits

  • Dust-proof and water-proof fan – protection class IP55.
  • Casing can be opened – easy service and cleaning access.
  • Cleaning with Pressure Washer 


Technical data AGRO HT

  AGRO HT3 AGRO HT5
Max. airflow [m3/h] 10 000 9 000
Heating capacity* [kW] 19,2-117 26,8-158
Power supply [V/Hz] 3x400 / 50
Max current consumption [A] 1,6
Max. power consumption [W] 630
IP 55 / F
Max acoustic pressure level **[dB(A)] 72,8
Max heating water temperature [oC] 95
Max operating pressure [MPa] 1,6
Connection 1”
Weight of unit [kg] [kg] 73 85
Weight of unit filled with water [kg] 83 102
Revolutions per minute [rpm] 955
Max.air stream without 6-SIDE OUTLET DIFFUSOR [m]*** 48 43
Max.air stream with 6-SIDE OUTLET DIFFUSOR [m/side]*** 15

*min. - temperature of heating medium 40/30o C, air temperature at the supply to the device 20o C;
  max. - temperature of heating medium 90/70o C, air temperature at the supply to the device 0o C
**acoustic pressure level has been measured 5 m from the unit in a 1500 m3 space with a medium sound absorption coefficient
***range of horizontal isothermal air stream, at 0,5 m/s velocity limit

Main dimensions AGRO HT

 

Heating capacities AGRO HT

AGRO HT3
Tp1 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2
°C kW l/h kPa °C kW l/h kPa °C kW l/h kPa °C kW l/h kPa °C kW l/h kPa °C
  Tw1/Tw2 = 90/70oC Tw1/Tw2 = 80/60oC Tw1/Tw2 = 70/50oC Tw1/Tw2 = 60/40oC Tw1/Tw2 = 50/40oC
V = 10 000m3/h
0 116 5099 46,9 32 100 4394 36,7 27,8 84,8 3699 27,5 23,5 69,4 3010 19,4 19,2 64,2 5556 60,6 17,8
5 107 4722 40,7 35,2 91,9 4027 31,2 30,9 76,6 3340 22,8 26,6 61,3 2660 15,4 22,3 56,2 4865 47,5 20,8
10 98,7 4352 35 38,3 83,7 3667 26,3 34 68,5 2988 18,6 29,7 53,4 2316 12 25,3 48,4 4189 36,1 23,9
15 90,5 3990 29,8 41,4 75,6 3313 21,8 37,1 60,6 2643 14,8 32,7 45,6 1977 9 28,3 40,7 3525 26,3 26,9
20 82,4 3634 25,1 44,5 67,7 2966 17,8 40,1 52,8 2303 11,5 35,7 37,8 1642 6,4 31,2 33,2 2873 18 29,8
25 74,5 3285 20,9 47,5 59,9 2625 14,2 43,1 45,2 1969 8,6 38,6 30,2 1309 4,2 34,1 25,8 2232 11,3 32,8
30 66,7 2942 17 50,5 52,2 2289 11,1 46 37,6 1638 6,2 41,5 22,5 974 2,5 36,9 18,4 1596 6,2 35,6
35 59,1 2605 13,6 53,4 44,7 1958 8,3 48,9 30 1308 4,1 44,3 14,4 623 1,1 39,5 11 953 2,4 38,4
AGRO HT5
Tp1 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2
°C kW l/h kPa °C kW l/h kPa °C kW l/h kPa °C kW l/h kPa °C kW l/h kPa °C
  Tw1/Tw2 = 90/70oC Tw1/Tw2 = 80/60oC Tw1/Tw2 = 70/50oC Tw1/Tw2 = 60/40oC Tw1/Tw2 = 50/40oC
V = 10 000m3/h
0 170 7515 138 47,2 149 6510 110 41,1 127 5517 83,4 35 105 4534 60 28,9 94,7 8200 180 26,2
5 158 6962 120 49,5 136 5971 93,5 43,4 115 4992 69,3 37,3 92,7 4021 48,2 31,1 83,1 7195 142 28,4
10 146 6421 104 51,8 124 5444 79 45,6 103 4478 56,9 39,5 81,1 3518 37,8 33,3 71,8 6212 109 30,6
15 134 5892 88,6 54 112 4929 65,9 47,8 91,2 3974 45,8 41,6 69,7 3024 28,7 35,3 60,7 5253 79,8 32,7
20 122 5375 74,9 56,2 101 4424 54 49,9 79,8 3489 35,9 43,7 58,4 2535 20,8 37,3 49,8 4311 55,6 34,8
25 110 4868 62,5 58,3 89,6 3929 43,5 52 68,7 2994 27,3 45,7 47,2 2050 14,1 39,2 39,1 3384 35,7 36,8
30 99,1 4371 51,3 60,4 78,5 3442 34,2 54,1 57,6 2513 19,8 47,7 35,9 1559 8,5 41 28,5 2464 20 38,7
35 88,1 3883 41,3 62,4 67,6 2963 26 56 46,7 2035 13,5 49,5 24 1041 4,1 42,5 17,7 1530 8,4 40,5
 

V – air flow
PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water stream flow in the heat exchanger
Δpw – water pressure drop in heat exchanger

AGRO HT devices can be installed vertical or under the ceiling with air outlet.

 

Outlet diffuser HT-C

6-sided air diffuser for AGRO HT under the ceiling installation enables steady air
distribution in entire volume of the room 

Rotary console AGRO HT

ensures easy access to the device, and optimal air flow around the device

Ceiling mount handles AGRO HT

a set of AGRO HT mounting brackets for under the ceiling installation

 

  • Manual

    (2.00 MB)

  • CAD

    (4.81 MB)

  • Product brochure

    (4.61 MB)

  • Catalogue cards

    (225.88 kB)

You are using Internet Explorer version 9.0 or earlier. For proper viewing of our website we recommend the latest version of the browser, which you can downloadhere.